/003H6751 Danfoss - AVQM PN25 DN20.webp)
PN: AVQM DN 20 / 003H6751
The Danfoss AVQM DN 20 (code 003H6751) combines a flow limiter and a motorized control valve in one body for district heating substations, connected by a G 1 A external thread.
It is a self-acting flow limiter with an integrated control valve for district heating, used with Danfoss AMV(E) 10/20/30 or spring-return AMV(E) 13/23/33 actuators; it closes when the set maximum flow is exceeded and needs no impulse tube. Rated PN 25 with a 12 bar maximum differential pressure and water up to 150 degrees C (140 degrees C continuous), it has a fixed internal differential pressure of 0.2 bar, a logarithmic characteristic, a control range above 1:50 and leakage of 0.01% of kvs. The DN 20 size has a kvs of 4.0 m3/h, a flow setting range of 0.07 to 2.2 m3/h and a 5 mm lift.
/084B8042_Danfoss.webp)
EXD 316 electronic expansion valve driver
/175N2584 Danfoss.webp)
VLT EtherNet/IP Modbus TCP gateway
/003H6750 Danfoss - AVQM PN25 DN15.webp)
Self-acting flow limiter with control valve, DN 15, G 3/4 A, PN 25
/003H6752 Danfoss - AVQM PN25 DN25.webp)
Self-acting flow limiter with control valve, DN 25, G 1 1/4 A, kvs 6.3, PN 25