Tan-Delta (Dissipation Factor) Test

Introduction

The Tan-Delta (Dissipation Factor) Test is a crucial diagnostic test for evaluating the condition of motor insulation. It helps detect insulation aging, contamination, and moisture absorption that could lead to motor failure.

This article explains the importance, procedure, and benefits of the Tan-Delta test and why it is essential for motor reliability.

Why Is the Tan-Delta Test Important? 

Motor insulation gradually degrades due to heat, electrical stress, and contamination. The Tan-Delta test measures the dielectric losses in insulation, helping industries:

  • Detect early-stage insulation deterioration
  • Identify moisture ingress or contamination
  • Assess insulation aging and performance
  • Ensure compliance with IEEE 286 and IEC 60034-27 standards

Unlike a simple Insulation Resistance (IR) Test, the Tan-Delta test provides a quantitative measurement of insulation quality, making it a more precise diagnostic tool.

How to Perform a Tan-Delta (Dissipation Factor) Test?

Equipment Needed:

  • Tan-Delta Tester (such as Omicron, Megger, or Doble test sets)
  • HV Power Supply (for applying high voltage)
  • Proper safety gear
  • Motor fully disconnected from power supply

Step-by-Step Procedure:

  1. Prepare the Motor:
  1. Connect the Test Equipment:
  • Connect the HV lead to the motor winding.
  • Connect the ground lead to the motor frame.
  • Ensure a proper guard connection to eliminate leakage currents.
  1. Apply Test Voltage:
  • Select the appropriate voltage level based on motor operating voltage:
    • 5 kV to 2 kV for low-voltage motors
    • Up to 12 kV for medium/high-voltage motors
  1. Measure the Tan-Delta (Dissipation Factor):
  • The tester applies AC voltage and measures the phase angle difference between voltage and current.
  • The test records the insulation loss factor (Tan δ) at different voltage levels.
  1. Evaluate the Test Results:
  • Tan-Delta values should be stable across different voltage levels.
  • A rising Tan-Delta value at higher voltages indicates insulation deterioration.
  • Compare results with past tests to track insulation degradation trends.

Interpreting Tan-Delta Test Results

Tan-Delta (Dissipation Factor) Value Insulation Condition
< 0.5% Excellent (New or well-maintained insulation)
0.5% – 1.5% Good (Minimal insulation degradation)
1.5% – 3.0% Moderate (Possible contamination or aging)
> 3.0% Poor (Severe insulation damage, urgent maintenance needed)

Benefits of the Tan-Delta (Dissipation Factor) Test

Early Detection of Insulation Aging – Helps prevent failures before they occur.
Identifies Moisture and Contamination – Finds issues not detected by basic resistance tests.
Ensures High Motor Reliability – Reduces the risk of sudden motor breakdowns.
Improves Predictive Maintenance – Allows better planning for insulation repairs.
Complies with IEEE & IEC Standards – Ensures safety and quality in insulation testing.

Best Practices for Tan-Delta Testing

  • Always test insulation at multiple voltage levels for accurate results.
  • Perform the test under controlled conditions to avoid environmental influences.
  • Compare current test results with historical data to track insulation health.
  • If Tan-Delta values are high, consider insulation drying or varnish treatment.

Conclusion

The Tan-Delta (Dissipation Factor) Test is one of the most reliable methods for assessing motor insulation health. It provides early detection of insulation failure risks, helping industries maintain efficient, safe, and long-lasting motor operations.

By incorporating Tan-Delta testing into a preventive maintenance strategy, businesses can reduce costly downtimes and ensure continuous industrial productivity.